FAQ Insulation & Vapor Barrier

Q.  What are the insulation R-values that I need for my home?

A.  At minimum, the walls require an R- 21, the ceiling must be R-38 and the foundation and rim boards must be a minimum of R-10.


Q.  How thick should my vapor barrier be?  Should it be hung tight?  Do I need to use tape and /or acoustic sealant?

A.  The vapor barrier must be at least 6 mils in thickness.  It should be hung neatly with some slack in the corners.  Tight corners cold tear when the sheetrock is hung and/or as the vapor barrier shrinks.  The use of tape is required when there is a seam that is not backed by framing.  This typically happens when the seam is placed at right angles to the framing.  Acoustic sealant is not required but is recommended.


Q.  Can I use spray foam in the crawl space and attic?

A.  Yes; however, any exposed spray foam or some brands of rigid insulation must be protected with a fire barrier such as fiberglass insulation, sheetrock or sheet metal.

Category: Building Department